Loading Arm Electrical

a)All electric cables shall be oil resistant and suitable for saliferous salty marine environment. The outer sheath of the cables used in intrinsically safe circuit shall be blue in color.
b)The 4 pole isolator switch shall be in the Contractor’s scope of supply. Contractor shall provide necessary means to derive the AC 230V, 1 phase, 50Hz supply for the operation of the motor starter current.
c)Electrical Motors shall be Ex-proof and shall meet the requirements of applicable codes and standards “IEC 60034, IEC 60072”. The power supply for theElectrical Motors shall be 400V +/- 10% AC, 3 Phase 4 wires, 50 Hz.
Contractorshall include “EExd” rated DOL starter c/w main isolator switch, indicators for power “ON”, “RUN” and “TRIPPED”.
Motor starter panel shall have ingress protection of at least IP55.
d)All the non-electrical metal parts of the assembly shall be bonded electrically using a 70 sq mm PVC insulated earthing cable in a ring system. Two numbers of M10 earthing bolts shall be provided at the bare structure for connecting the equipment to the main earthing grid system via PVC insulated earthing cable.The color of the earthing cables shall be “green/yellow”.
e)All interconnection material such as tubing, cabling, cable tray, conduit, etc shall be under Contractor scope of supply. Routine test as per the applicable codes and standards shall be conducted on the electric motors as per “IEC 60034, IEC 60072” and test certificates shall be furnished. Type test certificates and explosion proof certificate shall be furnished for review.